Technical specifications of testo 400 air flow meter
Temperature – NTC | |
---|---|
Measuring range | -40 to +150 °C |
Accuracy | ±0.2 °C ±1 digit (-25 to +74.9 °C)
±0.4 °C ±1 digit (-40 to -25.1 °C) ±0.4 °C ±1 digit (+75 to +99.9 °C) ±0.5 % measuring value ±1 digit (Remaining measuring range) |
Resolution | 0.1 °C |
Temperature – TC Type K (NiCr-Ni) | |
---|---|
Measuring range | -200 to +1370 °C |
Accuracy | ±(0.3 °C + 0.1 % measured value) ±1 digit |
Resolution | 0.1 °C |
Differential pressure (internal sensor) – Piezoresistive | |
---|---|
Measuring range | 0 to +200 hPa |
Accuracy | ±(0.3 Pa +1 % measured value) ±1 digit (0 to 25 hPa)
±(0.1 hPa +1.5 % measured value) ±1 digit (25.001 to 200 hPa) |
Resolution | 0.001 hPa |
* TUC connection (Testo Universal Connector): For connecting fixed cable digital probes and NTC probes.
Temperature – NTC | |
---|---|
Measuring range | -10 to +70 °C |
Accuracy | ±1.8 °C |
Resolution | 0.1 °C |
Air flow velocity/flow | |
---|---|
Measuring range | 0.6 to 50 m/s |
Accuracy | ±(0.2 m/s + 1% measured value) (0.6 to +40 m/s)
±(0.2 m/s + 2% measured value) (40.1 to 50 m/s) |
Resolution | 0.1 m/s |
Temperature – NTC | |
---|---|
Measuring range | -20 to +70 °C |
Accuracy | ±0.5 °C |
Resolution | 0.1 °C |
Air flow velocity/flow | |
---|---|
Measuring range | 0.3 to 35 m/s |
Accuracy | ±(0.1 m/s + 1.5% measured value) (0.3 to 20 m/s)
±(0.2 ms t1 1.5% measured value) (20.01 t2 35 m/s) |
Resolution | 0.01 m/s |
Temperature – NTC | |
---|---|
Measuring range | -20 to +70 °C |
Accuracy | ±0.3 °C (+15 to +30 °C)
±0.5 °C (Remaining range) |
Resolution | 0.1 °C |
Humidity – Capacitance | |
---|---|
Measuring range | 0 to 100 %rh |
Accuracy | ±(0.6 %rh + 0.7 % measured value) (0 to 90 %rh)
±(1.0 %rh + 0.7 % measured value) (90 to 100 %rh) ±0.03 %RH/K (k=1) long-term stability: ±1 %RH / year |
Resolution | 0.01 %rh |