Specifications
Model: FLUKE 1630 | |||
Measuring function | Scale | Accuracy | |
Earth resistance measurement | 0.025 – 0.250Ω | ±(1%+0.01Ω) | |
0.250 – 9.999Ω | ±(1%+0.01Ω) | ||
10.00 – 99.99Ω | ±(1.5%+0.1Ω) | ||
100.0 – 199.9Ω | ±(2%+0.5Ω) | ||
200.0 – 400.0Ω | ±(3%+1Ω) | ||
400.0 – 600.0Ω | ±(6%+5Ω) | ||
600.0 -1500Ω | ±(10%+10Ω) | ||
Measure current | 0.2mA – 1000mA | ±(2.5%+5mA) | |
0.2A – 30A | ±(2.5%+10mA) | ||
Low battery indicator | Have | ||
HOLD key holds the result | Have | ||
Save measurement results | Yes, up to 50 measurement results | ||
Auto shut off | Have | ||
Minimum resolution | 0.001Ω | ||
Pliers opening | 35mm | ||
Source | 4v AA 1.5V batteries | ||
Size | 276 x 100 x 47 mm | ||
Mass | 750g |
Detailed review of FLUKE 1630 earth resistance clamp meter
FLUKE 1630 Earth Clamp Meter is a new generation product line that makes measuring ground resistance simpler and more convenient by clamping the ground wire without having to insert a stake. In addition to the main function of measuring ground resistance, FLUKE 1630 Earth Clamp Meter also provides the ability to measure leakage currents from a few mA to load currents up to 30A.
Application of sensing solutions to measure ground resistance
Application of new solution to measure earth resistance by induction method, FLUKE 1630 Earth Clamp Meter It will not be necessary to use a stake, saving more time up to 90% by simply clamping the device around the ground wire, the result will be quickly displayed on the screen. In addition, measuring the ground resistance with a clamp meter is an extremely optimal solution in cases where it is necessary to measure the ground resistance in cases where other methods cannot be used, typically inside a building or the ground is covered with concrete.
Comprehensive solution with the ability to measure leakage current, AC current
In addition to the main function of measuring lightning protection ground resistance, FLUKE 1630 Earth Clamp Meter It is also equipped with the ability to measure leakage current with a scale of only 0.2mA to 1000mA, and the ability to measure alternating current with a scale of only 0.2A to 30A, providing a complete and comprehensive solution for constructing an outdoor lightning protection grounding system.
Self-calibration feature before measurement, providing absolute accuracy
Maintenance and calibration :
► We also have calibration certificate attached ( optional )
► Please re-calibrate after use for a certain period through our purchase store.
DISTRIBUTED BY:
Semiki instrumentation Co., Ltd
Email: sales@semiki.com
Office tel: +84 28 2253 3522
~DOING OUR BEST FOR YOU~