Force and mechanical measuring equipment
– Measure and control pH, ORP, EC (conductivity), DO (dissolved oxygen) with just 1 screen.
– Mount directly on walls, pipes or in electrical cabinets.
– Using new generation digital electrodes helps reduce noise.
– USB, RS485 connection.
– Alarm with sound, LED light and multi-color display.
+ HI510-0540: machine with 5 relays and 4 analog output ports
+ HI510-0320: machine with 3 relays and 2 analog output ports
Control Mode
The machine has 3 control modes: On/Off, Proportional and PID, allowing users to flexibly choose the appropriate mode, ensuring the most accuracy and chemical savings. Besides, the machine is integrated with the HELP feature to assist users when setting parameters.
HOLD Feature.
This feature is especially useful when control needs to be stopped for system maintenance. At that time, the machine will transmit a 22 mA analog output signal to external devices as if in alarm mode.
Setting Up a Warning System.
The warning system will automatically be activated if the measurement value exceeds the allowable threshold or abnormal activity occurs. The LED will then flash red and the control relays will enter the disabled state until the alarm clears.
RELAY
Built-in protection feature, separating high voltage and low voltage areas.
The machine has a maximum of 5 control relays and 1 electromechanical relay
– Each relay has a 5A protective fuse
– The bridges can be removed for easy wiring
– There are 2 types of relays: 2-contact relay and 3-contact relay
– Can set program relay on/off, Proportional, PID, cleaning, warning or HOLD
Analog and Digital output signals
– The machine has 4 Analog output signal ports to control or transmit data to data logger, PLC, SCADA and other control systems.
– Digital RS485 output signal can connect up to 32 devices, such as PC or other signal receiving devices.
Digital input signal
The machine is provided with 2 input signal ports to control the disable, clean or HOLD mode of the HI510.
Automatic Probe Cleaning Mode
Operating environments with special characteristics such as high fat content, many microorganisms, coloring agents, etc., the probe will need to be cleaned more often. The cleaning feature will allow users to set up a probe cleaning program, helping the device always have accurate measurement results.
STORING MEASUREMENT RESULTS
Maximum storage of 100 lots, 1 lot can contain 8600 measurement results.
The measurement result retention time can be set from 10 seconds to 3 hours.
Measurement results include:
– Measurement time.
– ID of electrode and controller.
– Set up control and alarm relays.
– Calibration information. With pH, Offset and Slope values will be saved.
SPECIFICATIONS
RS485 Electrode/Probe |
– pH/temperature electrode (purchased separately) + HI1006-18xx, HI1006-38xx, HI1006-48xx – ORP/temperature electrode (purchased separately) + HI2004-18xx, HI2004-28xx – EC/temperature electrode HI7630-28xx, HI7630-48xx (purchased separately) – Galvanic membrane DO electrode HI7640-18xx (purchased separately) – HI7640-58 optical DO electrode (purchased separately) |
Digital Input Signal |
2 independent, galvanically isolated inputs (for HOLD feature and electrode cleaning) ON mode: 5 – 24 VDC |
Relay (Max. 5 Points) |
1-contact and 2-contact relay (SPDT or SPST) at 5A – 250V Resistive load 5A – 30 VDC. Fuse protected: 5A, 250V slow blow fuse |
Warning Relay |
Relay 1 contact SPDT Resistive load 5A – 250 VAC, 5A – 30 VDC Fuse protected: 5A, 250V slow blow fuse |
Analog Output Signal |
2 or 4 output signals 0 – 22 mA (can be set to 0 – 20 mA or 4 – 20 mA), 22 mA when alarm mode is activated |
Analog Output Signal Accuracy |
± 0.2% full scale |
Installation directory |
II |
Electricity supply |
100 – 240 VAC ±10%; 50/60 Hz |
Electricity consumption |
15VA (maximum varies, depending on hardware configuration) |
Power supply input Overcurrent protection |
Slow blow fuse 2A, 250V |
Save Measurement Results |
Maximum 8600 records, 100 per lot |
Operating Environment |
-20 to 50oC; Maximum RH 100% non-condensing |
Bark |
single case ½ DIN; IP65; Nema 4X |
Mass |
About 1.6 kgs |
Guarantee | 12 months |
Supply Includes |
– HI510-0540: machine with 5 relays and 4 analog output ports, user manual. – HI510-0320: machine with 3 relays and 2 analog output signal ports, user manual. |
Accessories Purchased Separately |
pH/temperature electrode + HI1006-18xx, HI1006-38xx, HI1006-48xx + HI1016-18xx, HI1016-38XX, HI1016-48XX where xx is the cable length 05 m, 10 m, 15 m, 25 m, 50 m |
ORP/temperature electrode + HI2004-18xx, HI2004-28xx where xx is the cable length 05 m, 10 m, 15 m, 25 m, 50 m |
|
EC/temperature electrode HI7630-28xx, HI7630-48xx where xx is the cable length 05 m, 10 m, 15 m, 25 m, 50 m |
|
Galvanic membrane DO electrode HI7640-18xx where xx is the cable length 05 m, 10 m, 15 m, 25 m, 50 m |
|
HI7640-58 optical DO electrode where xx is the cable length 05 m, 10 m, 15 m, 25 m, 50 m |
|
HI510-01 electrical cabinet mounting accessories set |
|
HI510-02 wall mounting kit |
|
HI510-03 pipe fitting kit |